Wall Section: What It Shows, Typical Details, R-Values and a Free Wall Section Builder

Collage of wall sections: a brick, polyiso and CMU wall section and a steel stud wall drawn with the builder in this article, a steel wall section sheet at 1:25, 1:5 and 1:10 wall details, a 1:50 wall section beside its elevation, and a house building section

A wall section is a drawing of an exterior wall cut vertically, showing every layer from the cladding to the interior finish, with the materials, thicknesses and the way the wall meets the foundation, floors, windows and roof. It is drawn at 3/4" = 1'-0" or larger (1:20 to 1:25 in metric) and is where the building envelope is actually designed.

Our articles are still written by humans!

Get human written articles in your Google feed.

Add as preferred source aibimtool, opens in a new window

This guide covers what a wall section must show, how it differs from a building section and a detail, and real examples from architects' sets. It also has a free wall section builder: pick a typical wall or build your own from the outside in, and it draws the section and plan detail with proper hatches, works out the real (effective) R-value, checks it against the 2021 IECC for your climate zone, and gives you a DXF.

Free wall section builder

Start from one of six typical walls, change any layer, and the drawing and numbers update as you go. The DXF opens in AutoCAD, BricsCAD, DraftSight and LibreCAD, one unit is one inch, and every layer sits on an NCS layer name (A-DETL-MCUT for cut lines, A-DETL-PATT for hatching, A-ANNO-TEXT for keynotes). Everything runs in your browser; nothing is uploaded.

Wall section builder
Outside7-1/8" thick
1R-0
2R-0
3R-0.55
4R-21 / 6.88
Stud
Spacing
Cavity
Framing factor
%
5R-0.45
Inside
U-factor
0.061
Btu/h·ft²·°F · 0.35 W/m²K
Effective R
R-16.3
RSI 2.87 · air films included
Insulation on the label
R-21
26% lost to studs, webs and gaps
IECC 2021, climate zone
Fails
U-0.061 against a maximum of U-0.045 (Frame wall, IECC 2021 Table R402.1.2).Prescriptive route instead: R-30, or R-20 + R-5ci, or R-13 + R-10ci, or R-20ci (Table R402.1.3).
EXTERIORINTERIORLAP SIDINGWEATHER-RESISTIVE BARRIER7/16" OSB SHEATHING2x6 WOOD STUDS @ 16" O.C. W/ R-21 BATT INSULATION1/2" GYPSUM BOARDASSEMBLY U-FACTOR 0.061 BTU/H-FT2-F, EFFECTIVE R-16.3PARALLEL PATH, 25% FRAMINGINCL. AIR FILMS. VERIFY WITH PRODUCT DATA7-1/8"1TYPICAL WALL SECTIONSCALE: 3" = 1'-0"EXTERIORINTERIOR16" O.C.2PLAN DETAILSCALE: 3" = 1'-0"DRAWN WITH THE FREE WALL SECTION BUILDER, AIBIMTOOL.COM/BLOG/WALL-SECTION. CC0. NOT FOR CONSTRUCTION WITHOUT REVIEW.
How this is calculated, layer by layer
Outside air film R-0.17, inside air film R-0.68.
5/8" Lap siding (fiber cement or vinyl): R-0. Counted as R-0 (conservative)
1/16" Weather-resistive barrier: R-0. Counted as R-0 (conservative)
7/16" OSB sheathing 7/16 in.: R-0.55. Scaled by thickness from the cited per-inch value
5-1/2" 2x6 wood studs @ 16 in., R-21 high-density batt: R-21 in the cavity, R-6.88 through the stud. Product label R-value at full thickness
1/2" Gypsum board 1/2 in.: R-0.45. CMHA TEK 06-01C, Table 5
Wood studs: U = 25% / R(stud path) + 75% / R(cavity path), the parallel path method. Thermal bridges at floor edges, ties, clips and windows are not included.

The drawing is a typical wall section: one representative piece of wall between floor and ceiling, at 3" = 1'-0", plus a plan detail that shows the studs at their spacing. It does not draw the footing, floor edge, window head or parapet, because those depend on the project. Use it as the starting block of your detail sheet, not as the whole wall section.

What a wall section shows

A wall section answers one question for the contractor: what is this wall made of, in what order, and how thick is each layer. A complete one on a construction set shows:

  • every layer of the wall from outside to inside, with material, thickness and a keynote or text note
  • the structure: stud size and spacing, masonry unit, concrete thickness, reinforcement where it matters
  • the foundation or slab edge at the bottom, the floor-to-wall connections at each level, and the roof or parapet at the top
  • vertical dimensions: floor-to-floor heights, head and sill heights, top of wall, often as level markers
  • the water and air control layers: weather-resistive barrier, flashing at every window head and floor line, weep screeds, the air barrier and where it continues across joints
  • insulation type and R-value, and fire-rated layers where the wall is rated
  • callout bubbles to larger details for each connection that does not fit at this scale

The last point is how a set is organized. The wall section shows the whole height of the wall at a medium scale and points to 1-1/2" or 3" = 1'-0" details for the window head, the sill, the floor line and the parapet. In the US National CAD Standard, sections go on the 300 series of the architectural sheets (A-301, A-302) and details on the 500 series, though many offices put wall sections with the details on A-5xx sheets.

Wall section vs building section vs detail

DrawingWhat it cutsTypical US scaleTypical metric scaleWhat you read from it
Building sectionThe whole building1/8" or 1/4" = 1'-0"1:100 or 1:50Storeys, heights, stairs, spaces
Wall sectionOne exterior wall, full height3/4" = 1'-0" (1/2" to 1")1:20 or 1:25Layers, materials, floor and roof connections
DetailOne connection1-1/2" or 3" = 1'-0"1:5 or 1:10Flashing, fasteners, sealant, exact sizes

The building section below shows two floors and a basement of a house. The wall layers are noted in text, but at 1:50 the wall is a few millimeters thick on paper, so the drawing cannot show how it is built. That is the job of the wall section.

A building section through a two-storey house with a basement, showing the stair, the rooms on each floor, the floor build-ups noted in Turkish beside each slab, level markers from minus 2.50 to plus 7.50, and the pitched roof

A building section: storeys, stair and levels, with each floor's layers written as a list beside the slab. Reference: Sections of Villa K by Selim Senin on Behance.

Wall section examples

The sheet below has two wall sections at 1:25 through a factory building. The wall is drawn full height from the ground to the parapet, each slab edge is shown with its finish, and the right section also shows the interior wall cladding in elevation behind the cut. A title block on the right gives the sheet number, scale and who drew and checked it.

A wall section sheet at 1:25 with two full-height sections through a two-storey building, the ground hatched at the bottom, slab edges and parapet, leader notes on the right of each wall, section titles Section 2 and Section 3, and a vertical title block with sheet number 04

Two wall sections at 1:25 on one sheet, with the title block naming the sheet Wall Section. Reference: Wall Section 01 by Majid Hoseini on Behance.

A student set from an Egyptian university shows the classic arrangement: the elevation of a bay at 1:50 on the left, the wall section through it in the middle, and circles on the section that call out details, each with its own number.

A sheet with two elevations of a wall bay at 1:50 on the left and two wall sections in the middle, each with floor build-ups listed in Arabic with thicknesses in centimeters, level markers plus 0.90, plus 5.10 and plus 9.30, and detail callout circles numbered 5 to 9

Elevation and wall section side by side, with detail callouts on the section and each floor's layers listed with thicknesses. Reference: Working Elevations and Wall Sections by Omnia Gamal on Behance.

The next sheet in the same set is the details those circles point to, at 1:5 and 1:10: a window frame, a cladding fixing and a floor edge.

A detail sheet with enlarged circular details at 1:5 and 1:10 of a window frame, a stone cladding fixing and a floor edge, each with leader notes in Arabic and a detail number

The details called out from the wall section, at 1:5 and 1:10. Reference: Working Elevations and Wall Sections by Omnia Gamal on Behance.

One thing to know when you search for examples: in interior design, "wall section" is often used for what architects call an interior elevation, a flat view of one wall of a room with its finishes and fixtures. One of the "wall section" projects we found on Behance, for a clinic, was exactly that.

Typical wall sections and their real R-values

These are the six walls in the builder, run through it. The R-value on the insulation bag is not the R-value of the wall: studs, steel webs and the films of air at each surface change it, in both directions. "Effective R" includes all of it; the climate zones are where the wall meets the 2021 IECC U-factor tables (R402.1.2 residential, C402.1.4 commercial, "all other" buildings).

Wall, outside to insideThicknessInsulation on the labelEffective RU-factorIECC residential zonesIECC commercial zones
Lap siding, OSB, 2x6 @ 16" with R-21, 1/2" drywall7-1/8"R-21R-16.30.0610 to 20 to 4
Rainscreen siding, 1" XPS, OSB, 2x6 @ 16" with R-21, drywall8-7/8"R-26R-22.70.044all0 to 7
Brick veneer, 2" mineral wool, gypsum sheathing, 6" steel studs @ 16" with R-19, 5/8" drywall13-15/16"R-27.4R-18.00.0560 to 30 to 4
Brick veneer, 2" polyiso, 8" grouted CMU, 3/4" air space, drywall15-1/2"R-14.4R-18.20.055all0 to 7
8" concrete, 1" XPS, 2x4 @ 16" with R-13 inside, drywall13"R-18R-17.00.0590 to 50 to 7
Rainscreen siding, 3" mineral wool, 5-ply CLT 6-7/8"11-5/16"R-12.6R-22.50.044all0 to 7

Assumptions: 25% framing for wood studs, lap siding counted as R-0, cladding behind a vented air space not counted at all. No wall in the table meets commercial zone 8, which asks for U-0.037 for mass walls and U-0.032 for wood-framed walls.

Three things in that table are worth a closer look.

The 2x6 R-21 wall ends at R-16.3, not R-21. Solid wood conducts heat about three times better than a fiberglass batt, so the studs, plates, headers and corners form a second path through the wall. The parallel path method splits the wall into those two paths and averages them by area. How much of the wall is framing decides the answer, and it is more than people assume. Measurements of real US houses, which PNNL's Building America guidance relies on, put a typical 16" o.c. wall at around 25% framing once plates, headers, corners and extra studs are counted, well above the 9% the studs alone would suggest. The builder defaults to 25% and lets you change it:

Framing factor2x4 with R-132x6 with R-21
10% (best case)R-13.0, U-0.077R-19.7, U-0.051
16% (advanced framing)R-12.2, U-0.082R-18.2, U-0.055
20%R-11.6, U-0.086R-17.3, U-0.058
25% (typical 16" o.c.)R-11.0, U-0.091R-16.3, U-0.061
30%R-10.5, U-0.095R-15.4, U-0.065

The 2x4 row shows a quirk of the code. The IECC R-value table lets you build an R-13 wall in climate zones 0 to 2, but the U-factor limit for the same zones is U-0.084, which our 2x4 R-13 wall only meets at about 16% framing or less. The R-value table and the U-factor table give different answers for the same wall; you may use either, but you cannot mix them.

Steel studs cut the insulation in half. A 3-5/8" steel stud wall with R-13 batts at 16" o.c. has an effective R of 6.0 for the stud layer, not 13; 6" studs with R-21 batts get R-7.4. Those numbers come from the Washington State Energy Code's steel framing table, which we used because it is published and free; the method behind it is the ASHRAE zone method. As a check, the builder's R-13 steel stud wall with 1/2" sheathing and 1/2" drywall comes out at U-0.126 against the 0.124 in the code's assembly table, and U-0.110 against 0.108 at 24" o.c. This is why the commercial IECC asks for R-13 plus continuous insulation on steel studs in every climate zone: the batts alone do not get there.

Concrete is not insulation, and CMU depends on what is in the cores. Normal-weight concrete is about R-0.08 to R-0.11 per inch, so an 8" wall is around R-0.9, and R-1.7 with its air films. Concrete block values from the masonry industry's TEK 06-02C table, with films:

8" CMUEmpty coresPerlite-filledFoam-filledSolid grouted
105 pcf (lightweight)R-2.3R-5.8R-6.4R-1.9
135 pcf (normal weight)R-2.0R-3.9R-4.1R-1.7

Grouting the cores for structure removes almost all the block's own resistance, which is why the CMU wall in the first table has 2" of polyiso outside. On the other hand, mass walls get a much easier U-factor limit than frame walls (U-0.082 against U-0.045 in residential zone 5), because heavy walls store heat and even out temperature swings.

The CLT wall shows the reverse surprise: wood is a reasonable insulator, about R-1.25 per inch, so a bare 5-ply panel is already R-9.4 with films and meets the residential mass wall limit in zones 0 to 2 without any insulation. The 2021 IECC counts mass timber as a mass wall for residential buildings (R402.2.5). For commercial buildings the mass wall definition in C402.2.2 is based on weight and heat capacity, and whether a given CLT panel meets it depends on its density, so the builder checks CLT against the stricter wood-framed column and tells you so.

How the builder calculates

Each number in the builder comes from a published source, linked in the "How this is calculated" panel under the drawing. In short:

  • Wood studs: parallel path, U = framing% / R(through the stud) + cavity% / R(through the insulation), the method used in ASHRAE Fundamentals and PNNL's Building America guides. Our code reproduces PNNL's worked example exactly (R-21.44 between studs, R-9.32 through the studs).
  • Steel studs: the stud and cavity layer is replaced by its effective R from the Washington State Energy Code table, then all layers add in series.
  • Everything else: layers in series, plus an outside air film of R-0.17 and an inside film of R-0.68. Behind a vented cladding, the cladding and the air space are not counted and the outside film becomes still air (R-0.68).
  • Code check: the U-factor rounded to three decimals against the IECC 2021 maximum for the zone, residential or commercial, with the prescriptive R-value route shown beside it.

What it leaves out: thermal bridges at floor edges, brick ties, cladding clips and window frames, which in steel and concrete buildings can matter as much as the insulation choice; moisture and condensation; fire ratings; and structural design. A wall that passes here passes the assembly U-factor check, nothing more. For a permit, the numbers need to come from your product data and, for commercial work, usually from COMcheck or REScheck.

R-19 batts deserve a note: an R-19 batt is 6-1/4" thick, and squeezed into a 5-1/2" 2x6 cavity it performs at about R-18, per the Insulation Institute's compression chart. The builder uses R-18 for it. R-21 high-density batts are made to fit 5-1/2" and keep their label value.

Wall sections in Revit, AutoCAD and IFC

In Revit, a wall section starts with the wall type: Edit Type, then Structure, where each layer gets a function (Structure, Substrate, Thermal/Air Layer, Finish), a material and a thickness, and the layers between the core boundaries define the structure. A section view at 3/4" = 1'-0" with the detail level set to Fine shows the layers with their cut patterns, and detail components, repeating details (brick, batt insulation) and keynotes turn it into a construction document. Revit also reports a Heat Transfer Coefficient (U) and Thermal Resistance (R) in the wall type's analytical properties, but it adds the layers in series from each material's thermal properties. A stud layer counts as solid wood or as insulation, never both, so for a framed wall Revit's number is too optimistic. Use the builder's effective R and write it in the type's description or a shared parameter. The "Copy layer table" button gives you the layers and thicknesses to retype.

In AutoCAD, wall sections are usually drawn from an office library of typical sections: lines for each layer, hatches for the materials, and a batt insulation linetype or block. The DXF from the builder fits that workflow. It is an R12 file, the oldest DXF version every CAD program opens, so the hatches arrive exploded into lines on the A-DETL-PATT layer; turn that layer off and rehatch in your office standard if you prefer associative hatches. The patterns themselves (sand for gypsum, rigid and soft insulation, brick and concrete) are from our free hatch pattern library, where each one is also a .pat file. We opened every preset's DXF with the ezdxf auditor, with no errors.

In IFC, an exterior wall carries its layers as an IfcMaterialLayerSet and its U-value as Pset_WallCommon.ThermalTransmittance, in W/m²K (the builder shows the SI value under the U-factor). In AIBIMTool's BIM workspace, picking a layered wall type in the Properties panel saves it to the IFC as an IfcMaterialLayerSet, and the free IFC editor lets you add ThermalTransmittance and IsExternal to the walls of any IFC file and save it again, so the energy number travels with the model instead of living only on the drawing. For how drawings come out of an IFC model, see IFC drawings.

Drawing a wall section by hand or in CAD

If you draw one from scratch, the order that avoids rework is:

  1. Fix the wall assembly first: the layers and thicknesses, outside to inside. The builder above is one way to do that and check the energy code before anything is drawn.
  2. Cut the section where the wall is most typical and where it has the most going on, usually through a window so the head and sill appear.
  3. Draw the structure first (footing, slab, floor framing or slabs, roof structure), then the wall layers, then the openings.
  4. Hatch each cut material with its standard pattern. Leave elevation lines beyond the cut thin and unhatched.
  5. Add level markers, the vertical dimensions and the overall wall thickness.
  6. Note every layer with a keynote or leader text, in capitals, outside to inside, and the same way on every wall section in the set.
  7. Circle each connection that needs more detail and number it to the detail sheet.

The keynote text in the builder follows the usual CD style, for example 2x6 WOOD STUDS @ 16" O.C. W/ R-21 BATT INSULATION and 1/2" GYPSUM BOARD, so it can be pasted into an existing set without rewording. For what else goes on a construction set and in which order, see architectural drawings; for the sheet frame itself, our title block templates; and for the window sizes, sill heights and U-factors that sit in the wall, the door and window schedule guide.

Frequently asked questions

What is a wall section in architecture?

A wall section is a drawing of an exterior wall cut vertically, usually from the footing or slab up to the roof or parapet, at a scale large enough to show every layer: cladding, air space, insulation, sheathing, framing or masonry, interior finish, and how the wall meets the foundation, each floor, the windows and the roof. It sits between the building section, which shows the whole building at a small scale, and the details, which zoom into single connections.

What is the difference between a wall section and a building section?

A building section cuts through the whole building to show storeys, heights, stairs and spaces, at 1/8 or 1/4 inch to the foot (1:100 or 1:50). A wall section cuts through one exterior wall only, at 3/4 inch to the foot or larger (1:20 or 1:25), and shows how the wall is built: materials, thicknesses, flashing, insulation and the floor and roof connections. The building section tells you where the wall section is taken.

What scale is a wall section drawn at?

In US practice a full-height wall section is usually drawn at 3/4 inch = 1 foot, sometimes 1/2 inch or 1 inch = 1 foot, and the details called out from it at 1-1/2 or 3 inches = 1 foot. In metric sets wall sections are 1:20 or 1:25 and details 1:5 or 1:10. The builder in this article draws a typical wall section at 3 inches = 1 foot (1:4), which is detail scale, because it shows one typical piece of wall rather than the full height.

What is the R-value of a 2x6 wall?

Not R-21, even with R-21 batts. With lap siding, 7/16 inch OSB, R-21 batts in 2x6 studs at 16 inches on center and 1/2 inch drywall, the whole wall works out at about R-16.3 (U-0.061) using the parallel path method and 25 percent framing, air films included. With advanced framing at 16 percent framing it is about R-18.2. Adding 1 inch of XPS outside brings it to about R-22.

What is the R-value of an 8 inch concrete wall?

Very low. Normal-weight concrete has an R-value of roughly 0.08 to 0.11 per inch, so 8 inches is about R-0.9, and the bare wall with its two air films is about R-1.7 (U-0.58). Concrete walls meet energy codes through added insulation, usually rigid board outside or a furred stud wall inside. An empty 8 inch lightweight concrete block is about R-2.3 with air films, and about R-5.8 with perlite-filled cores.

What is the effective R-value of a steel stud wall?

Roughly half the batt's label. The Washington State Energy Code table gives R-13 batts in 3-5/8 inch steel studs at 16 inches on center an effective R-6.0 for the stud and cavity layer, and R-21 batts in 6 inch studs R-7.4, because the steel studs conduct heat around the insulation. That is why commercial energy codes require continuous insulation outside steel stud walls in every climate zone.

More articles

Collage of architectural drawings: a building section with grid lines and dimensions, an axonometric of a villa, a front elevation, a site plan with the street, a reflected ceiling plan and a hatched stair detail
Workflows and Tutorials

Architectural Drawings: 12 Types, Scales and How to Read Them

What architectural drawings are, the 12 types in a full drawing set with real examples, US scales, sheet numbers like A-101, the drawings each project phase produces and how to read them.

19 min read
Collage of title blocks: a villa construction sheet with a grey vertical title block, revision table and approval codes, the rotated project name of an apartment building sheet, a Revit title block in Spanish, and the ISO and US title block templates from this article
Workflows and Tutorials

Title Block: What It Is, What Goes in It, and Free Templates (DXF, PDF)

What a title block is, the fields every drawing sheet needs, where it goes on US and ISO sheets, real examples, how to add one in AutoCAD and Revit, and five free title block templates as DXF and PDF.

18 min read
Collage of door and window schedules on architects' sheets, with door elevations, frame types and a door schedule table made from an IFC model
BIM and IFC

Door Schedule: What Goes in It, Examples, Free Templates and an IFC Schedule Maker

What a door schedule and a window schedule contain, column by column, how doors are numbered, what the fire rating column means, real examples, free XLSX templates, and a free tool that builds door, window and room finish schedules from an IFC model. Includes our test of 19 real IFC files.

16 min read